LED flash light Overhead line fault locator and fault detector
Technical Parameters
HSFI series overhead line short-circuit fault indicators
· Short-circuit Fault Detection:
If/I0 is larger than the tuning value of the fault current (The value rang is between 1.0A~60A,can be adjusted automatically), in which I0 is the load current and should greater 3A; If is the fault current and should greater 200A, the line voltage is lower than 3000V.
· Over Current Fault Detection:
Automatic setting the line fixed over current (the stepping is 50A), line current> fixed over current and delay tripping( the line current is 0).
· Line Voltage: No limitation
· Line Type: Overhead line(insulated, bare wires)
· Reset:
For transient faults, reset based on the given time(12 hours) by default;
For permanent faults, reset when power is up.
·Alarming:
Red flag and LED flash light
·Power: ≤3μA
·IP Protection Class: IP67
·Temperature: -40°C~+70°C
·Lifetime: Over 10 years
HESI series overhead line earth and short-circuit fault indicators
· Short-circuit Fault Detection:
If/I0 is larger than the tuning value of the fault current (The value rang is between 1.0A~60A,can be adjusted automatically), in which I0 is the load current and should greater 3A; If is the fault current and should greater 200A, the line voltage is lower than 3000V.
· Over Current Fault Detection:
Automatic setting the line fixed over current (the stepping is 50A), line current> fixed over current and delay tripping( the line current is 0).
· Earth Fault Detection:
The RMS value of sudden changes on the transient current in 3ms Ip is no less than 15A, the line voltage is lower than 3000V for over 15s (the period can be tuned).
· Line Voltage: No limitation
· Line Type: Overhead line(insulated, bare wires)
· Reset:
For transient faults, reset based on the given time(12 hours) by default;
For permanent faults, reset when power is up.
·Alarming:
Red flag and LED flash light
·Power: ≤3μA
·IP Protection Class: IP67
·Temperature: -40°C~+70°C
·Lifetime: Over 10 years
Technical index | Overhead earth and short-circuit fault detector | Overhead earth and short-circuit fault detector | Overhead short-circuit fault detector | Overhead short-circuit fault detector |
Model | HESI-FG | HESI-FLG | HSFI-FS | HSFI-FLS |
Fault type | earth/short-circuit | earth/short-circuit | Short-circuit | Short-circuit |
Applicable Voltage grade | 6-35kV | 6-35kV | 6-35kV | 6-35kV |
Applicable wire cross-section | 16-400 mm2 | 16-400 mm2 | 16-400 mm2 | 16-400 mm2 |
Standard reset time | Adjustable | Adjustable | Adjustable | Adjustable |
Times of actuating | Over 5000 | Over 5000 | Over 5000 | Over 5000 |
Static power consumption | 1uA | 1uA | 1uA | 1uA |
Applicable ambient temperature | -40°C~70°C | -40°C~70°C | -40°C~70°C | -40°C~70°C |
Relative humidity | Daily mean ≤95% | Daily mean ≤95% | Daily mean ≤95% | Daily mean ≤95% |
Maximum elevation | 4000m | 4000m | 4000m | 4000m |
Contamination grade | IP67 | IP67 | IP67 | IP67 |
Indication mode | Red flag | Red flag+ LED flash light | Red flag | Red flag+ LED flash light |